19
Item Valid Range
Zone Type 0 = Not Used
1 = Burglar
2 = 24 Hour Fire
3 = 24 Hour Holdup
4 = 24 Hour Auxiliary
5 = Momentary Keyswitch (Arm
AWAY/Disarm)
6 = 24 Hour Communicator
7 = 24 Hour Burglar Tamper
8 = Universal
9 = Universal Logged
10 = Verified Fire
11 = Fire Supervisory
12 = Listen-In Module Input
Area Number 0 = Disable
1 = Area 1
2 = Area 2
Expansion Zone 0 = ZXEXP Zone
1 = RF Gateway 1 Zone
2 = RF Gateway 2 Zone
3 = ZEM Zone
Burglar Zone Attributes 00 to FF
(see the Burglar Zone
Attribute Table.)
Zone Attributes 00 to FF
(see the Zone Attribute Table.)
Description
Critical Condition Monitor (CCM), no local display
May be used to activate an output that is programmed as
Universal. Only the Universal Logged is posted in the Event
Log when activated. No events are reported to the Central
Station.
Upon activation, control resets switched smoke power. The
loop is ignored for 30 seconds. Subsequent activation within
the next 60 seconds causes an alarm.
See Section 3.3, Programming Note 11.
Determines which area the zone belongs to. Fire zones are
visible to both areas regardless of settings.
Determines which data bus device the system will poll to get
the zone’s status data.
Reserved for future use.
Reserved for future use.
Reserved for future use.
See Section 3.3, Programming Notes 2, 6, and 7 for a
complete description of the Burglar Zone Attributes.
Bell Output on Alarm - determines if Bell Output activates
due to an alarm from the zone. See Section 3.3, Programming
Note 8.
Keypad Sounder on Alarm - determines if control station
sounder activates due to an alarm from the zone. See Section
3.3, Programming Note 8.
Bypassable - determines if a zone may be bypassed or force-
armed. See Section 3.3, Programming Note 9.
Senior Watch - see Section 3.3, Programming Note 10.
Zone Supervision - determines how opens and shorts are
handled.
Fast Zones - only applies to zones 1 - 12. A Fast Zone on
zones 1 - 6 has a loop response time of 80 msec. A Fast Zone
on zones 7 - 12 has a loop response time of 20 msec.
The following table refers to programming locations 35 - 166.
Note: Zone 29 & 30
may only be pro-
grammed as 24 Hour
Fire, Verified Fire or
Not Used; any other
will be interpreted as
Not Used. All other
zones may be
programmed as any
zone type.
WWW.DIYALARMFORUM.COM